ZBW17(YB)-10 Series Prefabricated Substation is used in 10/0.4kV, 50Hz power distribution system with a transformer rated capacity of 50~1600kVA. It is widely used in outdoor power supply fields such as city, residential zone, factory and mining, hotel, hospital, park, oil field, airport, wharf, railway and other temporary facilities, etc.
1. Product Introduction
ZBW17 (YB)-10 Series Prefabricated (American Type) Substation is the series product in our company and it be developed by ourselves through absorb foreign technique. The transformer, load switch and H.V fuse are installed in transformer’s cabinet and take the insulating liquor of transformer as the insulating medium and heat-eliminating medium for whole product,it features of small volume,light weight,installation and maintenance are convenient,high safe reliability,beautiful appearance,etc.
2.Product Parameter (Specification) of ZBW17(YB)-10 Series Prefabricated Substation
Table 1 Parameters of load switch
NO. |
Name |
Unit |
Parameters |
1 |
Rated voltage |
kV |
12 |
2 |
Rated current |
A |
630 |
3 |
Rated frequency |
Hz |
50 |
4 |
Rated breaking current |
A |
630 |
5 |
Rated short-time withstand current |
kA |
16/2 |
6 |
Rated peak withstand current |
kA |
40 |
7 |
Full load breaking times |
time |
20 |
8 |
Mechanical endurance |
time |
2000 |
9 |
1 min power frequency withstand voltage (phase to phase and phase to earth) |
kV |
42 |
10 |
Lightning impulse level (phase to phase and phase to earth) |
kV |
75 |
Table 2 Parameters of H.V cable plug
NO. |
Name |
Unit |
Parameters |
1 |
Rated voltage |
kV |
12 |
2 |
Rated current |
A |
200,300,630 |
3 |
1 min power frequency withstand voltage |
kV |
42 |
4 |
Insulation resistance |
MΩ |
2000 |
5 |
Contact contacting resistance |
µΩ |
≤100 |
Table 3 Parameters of fuse
In support style current limiting fuse and plug-in type fuse are all oil immersed type.
Rated capacity (kVA) |
Rated voltage (6kV) |
Rated voltage (10kV) |
||
Current limiting fuse (A) |
Model of plug-in type fuse |
Current limiting fuse (A) |
Model of plug-in type fuse |
|
50 |
40 |
C06 |
40 |
C04 |
100 |
50 |
C08 |
40 |
C06 |
160 |
80 |
C10 |
50 |
C08 |
200 |
80 |
C10 |
80 |
C10 |
250 |
125 |
C10 |
80 |
C10 |
315 |
150 |
C12 |
80 |
C10 |
400 |
150 |
C12 |
100 |
C11 |
500 |
175 |
C14 |
125 |
C12 |
630 |
175 |
C14 |
150 |
C12 |
800 |
200 |
C16 |
150 |
C14 |
1000 |
200 |
C16 |
200 |
C16 |
1250 |
200 |
★ |
200 |
C16 |
Table 4 Technical parameters of transformer
Rated capacity(kVA) |
No-load loss (W) |
Load loss (W) |
Impedance voltage % |
||
S9 |
S11 |
S9 |
S11 |
||
50 |
170 |
120 |
870 |
870 |
4
|
100 |
290 |
200 |
1500 |
1500 |
|
160 |
400 |
280 |
2200 |
2200 |
|
200 |
480 |
335 |
2600 |
2600 |
|
250 |
560 |
390 |
3050 |
3050 |
|
315 |
670 |
465 |
3650 |
3650 |
|
400 |
800 |
560 |
4300 |
4300 |
|
500 |
960 |
670 |
5100 |
5150 |
|
630 |
1200 |
840 |
6200 |
6200 |
4.5 |
800 |
1400 |
980 |
7500 |
7500 |
|
1000 |
1700 |
1190 |
10300 |
10300 |
|
1250 |
1950 |
1365 |
12000 |
12000 |
3. Service ambient conditions ofZBW17(YB)-10 Series Prefabricated Substation
a. Altitude above sea level: ≤1000m
b. Ambient temperature range: Max. +40℃;
Min. -35℃
c. Relative humidity: Daily average don’t exceed 95% and monthly average value don’t exceed 90%
d. Wind speed (outdoor): Not more than 35m/s
e. Installation spot: There should be no fire, explosion, badly polluted, chemical erode and strong vibration. If the condition is out of above normal service environment, the customer can consult with us to resolve it.
4. Product Features ofZBW17(YB)-10 Series Prefabricated Substation
Total-sealed, total-insulated, safe and reliable.
Small volume and compact structure.
The cable head can be operated with the load of 200A.
Has strong over-load ability.
The body of substation adopts special craftwork treatment and has well anticorrosion ability.
Use high burning point oil to avoid the fire.
Has beautiful appearance and assort with environment