VT2A (ZN73C) Series indoor HV Vacuum circuit breaker in line with GB 1984, IEC 62271 and other domestic and international standards and reliable interlock function.
VT2A (ZN73C) Series indoor HV Vacuum circuit breaker
1. Product Introduction
VT2A (ZN73C) Series indoor HV Vacuum circuit breaker is a three-phase AC 50Hz, indoor 6-10kV power system switchgear, as industrial and mining enterprises, power plants and substation control and protection of electrical facilities unit. Due to the special advantages of vacuum circuit breaker, in particular, the applicable requirements of the rated operating current frequent operation, or multiple short-circuit breaking current location.
2. Type meaning of VT2A (ZN73C) Series
indoor HV Vacuum circuit breaker
V
T 2 A ( Z N 7 3 C ) - 12 (0)/ 0 - 0
V: vacuum circuit breaker
T: Tianan Electric
2A: Design Number
ZN73C: Industry Model
12: Rated voltage kV
(0): Structure, A open; B solid sealing
0: Rated current
0: Rated short-circuit breaking current kA
3. The main technical parameters of VT2A (ZN73C) Series indoor HV Vacuum circuit breaker
No. |
Item |
Unit |
Parameters |
|
1 |
Rated voltage |
kV |
12 |
|
2 |
Rated frequency |
Hz |
50 |
|
3 |
Rated lightning impulse withstand voltage: phases , earthing / fracture between |
kV |
75/85 |
|
4 |
Rated 1min power frequency withstand voltage:phases , earthing / fracture between |
kV |
42/48 |
|
5 |
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
|
6 |
Rated current |
A |
630,1250 |
1250,1600 |
7 |
Rated short circuit breaking current |
kA |
20/25 |
31.5 |
8 |
Rated short-circuit current (peak) |
kA |
50/63 |
80 |
9 |
Rated short duration |
S |
4 |
|
10 |
Breaking times |
time |
100 |
50 |
11 |
Mechanical life |
time |
20000 |
|
12 |
Weight |
kg |
75 |
4. Structure Introduction
VT2(ZN73C)-12 Type indoor high
voltage vacuum circuit breaker overall structure before and after the
interrupter operating mechanism and lined up in the form of arrangement, the
dominant part of a three-phase electrical circuit floor-standing institutions.
Vacuum interrupter mounted longitudinally in a tubular insulating tube,
insulation tube using an epoxy resin APG process from casting, so it is
particularly anti-creepage. This design greatly reduces dust accumulation on
the surface of the interrupter can not only prevent the vacuum interrupter
affected by external factors, but also to ensure that even under severe hot and
humid and dirty environment also can exhibit high voltage effect impedance
state.
5.
Ordering Information for VT2(ZN73C)-12 Type indoor high voltage vacuum circuit
breaker
1.
breakers name, type, size and number of orders
2. The circuit breaker rated voltage, rated current and rated breaking breaking
current
3. Optional element program
4. Rated operating voltage
5. spare, the name and quantity of spare parts
6. If there are other special customer requirements, when ordering