VT19-40.5 Indoor HV Vacuum Circuit Breaker VT19-40.5 Indoor HV Vacuum Circuit Breaker is in line with GB/T 1984" HV AC CB, JB/T3855" 3.6 - 40.5kV indoor HV AC vacuum CS" and IEC standards. CB has reliable inter10ck function, can not only be as a handcart unit but also a fixed unit.
VT19-40.5 Indoor HV Vacuum Circuit Breaker
1. Product Introduction
VT19-40.5 Indoor HV Vacuum Circuit Breaker is the electric system switchgear with three phase AC of 50Hz, 40.5kV. It is also as the control and protection unit of industrial enterprises and mines, power station and substation device. VT19-40.5 Indoor HV Vacuum Circuit Breaker can be proceeded frequent operation and has many times breaking and rapid reclosure capacity, and has reliable interlock function.
2.Product
Parameter (Specification) ofVT19-40.5
Indoor HV Vacuum Circuit Breaker
S/N |
Parameter Name |
Unit |
Data |
1 |
Rated Voltage |
KV |
40.5 |
2 |
Rated Frequency |
Hz |
50 |
3 |
Rated Lightning Impulse withstand voltage |
KV |
185 |
4 |
Rated 1 min Power Frequency withstand voltage |
KV |
95 |
5 |
Rated Operation Sequence |
|
Q.0.3s.CQ.180s.CQ |
Model of Cb |
Rated Current |
Rated Breaking Current |
Rated short circuit making current(Peak) |
Rated duration of short circuit |
Rated breaking times of short circuit(times) |
Mechanical life (times) |
|
VT19-40.5 Indoor HV Vacuum Circuit Breaker |
630 |
20/25 |
50/60 |
4 |
30 |
10000 |
|
1250 |
|||||||
1250 |
|||||||
1600 |
31.5 |
80 |
4 |
20 |
10000 |
||
2000 |
|||||||
3150 |
|||||||
3.Service Condition of VT19-40.5 Indoor HV Vacuum Circuit Breaker
Normal Condition
Ambient Temperature: +40℃--15℃
Ambient Humidity
Daily Average Relative Humidity s95%
Daily Average Vapour Pressure S2.2x10-³ MPa
Monthly Average Relative Humidity s90%
Monthly Average Vapour Pressure s1.8x10-³Mpa
Attitude ≤1000m Earthquake Intensity < grade 8
Installation spot: The spot should have no water, explosion danger, serious pollution, chemical corrosion and exquisite shake.
4.STORAGE AND TRANSPORTATION for VT19-40.5 Indoor HV Vacuum Circuit Breaker
Transportation
VT19-40.5 Indoor HV Vacuum Circuit Breaker is packaged individually, fìxed on the inner frame and made the appropriate protection, when circuit breaker is lifting, lifting hook hanging on the lifting hole that is clearly identified circuit breaker. When carring, does not force the upper and lower arm, at the same time it should not make a greater shock and vibration to circuit breaker
Storage
Before operating, the VT19-40.5 Indoor HV Vacuum Circuit Breaker must be stored in a dry, dust-free and ventilated place. At the same time the circuit breaker must be in the opening position, and the tension spring mechanism is discharged