VS1-12 Indoor AC Vacuum Circuit Breaker is used as protection and control unit of three-phase AC indoor medium voltage switchgear and industrial and mining enterprise power device of 50Hz and rated voltage up to 7.2~24kV. VS1-12 Indoor AC HV Vacuum Circuit Breaker complies with IEC60694, IEC62271-100
VS1-12 Indoor AC Vacuum Circuit Breaker
1. Product Introduction
VS1-12 Indoor AC Vacuum Circuit Breaker is the electric system switchgear of rated voltage 12kV/24kV.lt is also as the control and protection unit of industrial enterprises and mines, power station and substation device. VS1 Series Indoor AC HV Vacuum Circuit Breaker can be proceeded frequent operation and has many times breaking and rapid reclosure capacity, and has reliable interlock function. The CB is in line with GB/T1984-2014"AC HV CB" ,JB/T3855-2008 “3.6-40.5kV indoor AC HV vacuum CB", DLlT403-2000 “10-40.5kV HV vacuum CB ordering technical condition" and IEC62271-100:2008 . The device is front and back split charging structure, not only as a fixed installation unit but also match handcart unit with base plate cart. Intelligent components can be selected to realize on-line monitoring and fault diagnosis of contact temperature, mechanical characteristics and partial discharge. Remote monitoring and maintenance can be achieved through mobile phones and Internet of Things cloud platform .
2.Product Parameter (Specification) of VS1-12 Indoor AC Vacuum Circuit Breaker
voltage vacuum circuit breaker
No. |
Description |
Unit |
Data |
||||
1 |
Rated voltage |
kV |
12 |
||||
2 |
Rated insulation levels |
Rated power frequency withstand voltage/1min |
|
42 |
|||
Rated lighting impulse withstand voltage |
75 |
||||||
3 |
Rated frequency |
Hz |
50 |
||||
4 |
Rated current |
A |
630 |
630 |
1250 |
1600 |
|
1250 |
1250 |
1600 |
2000 |
||||
|
|
2000 |
2500 |
||||
|
|
2500 |
3150 |
||||
|
|
|
4000 |
||||
5 |
Rated short circuit breaking current |
kA |
20 |
||||
6 |
Rated short time withstand current(4s) |
kA |
20 |
||||
7 |
Rated short circuit making current |
kA |
50 |
||||
8 |
Rated peak value of withstand current |
kA |
50 |
||||
9 |
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
||||
10 |
Rated short circuit breaking current breaking times |
times |
30/20(40kA) |
||||
11 |
Rated cable charge breaking current |
A |
25 |
||||
12 |
Rated single capacitor bank breaking current |
A |
630/400(40kA) |
||||
13 |
Rated back to back capacitor bank breaking current |
|
400 |
||||
14 |
Mechanical life |
times |
10000 |
||||
16 |
Allowed abrade cumulative thickness of moving and static contactor |
mm |
3 |
||||
17 |
Clearance between open contacts |
mm |
11±1 |
||||
18 |
Contact stroke |
mm |
3.5±0.5 |
||||
19 |
Bounce duration of contact closing |
ms |
≤2 |
||||
20 |
Non-simultaneity of three phase for opening and closing |
ms |
≤2 |
3. Service Condition of VS1-12 Indoor AC Vacuum Circuit Breaker
Ambient Temperature:+40'C--15'C
Ambient Humidity: Daily average relative humidity≦ 95%
Monthly average relative ≦90%
Monthly average vapour pressure≦ 1.8 x 10 -³~pa
Altitude≦1000m
Earthquake intensity < grade 8
Installation spot: The spot should have no water, explosion danger, serious pollution, chemical corrosion and exquisite shake
4.STORAGE AND TRANSPORTATION
Transportation
VS1-12 Indoor AC Vacuum Circuit Breaker is packaged individually, fixed on the inner frame and made the appropriate protection, when circuit breaker is lifting, lifting hook hanging on the lifting hole that is clearly identified circuit breaker. When carrying, does not force the upper and lower arm, at the same time it should not make a greater shock and vibration to circuit breaker.
Storage
Before operating, the VS1-12 Indoor AC Vacuum Circuit Breaker must be stored in a dry, dust-free and ventilated place. At the same time the VS1-12 Indoor AC Vacuum Circuit Breaker must be in the opening position, and the tension spring mechanism is discharged