LW 39-126/T 3150-31.5, 40 Outdoor HV AC SF6 Circuit Breaker is applied in power system with 50Hz frequency, 110kV system normal voltage. It is the main power equipment used in power plant and substation for control and protection.
1.Introduction of LW 39-126/T 3150-31.5, 40 Outdoor HV AC SF6 Circuit Breaker
LW 39-126/T 3150-31.5, 40 Outdoor HV AC SF6 Circuit Breaker is equipped with CT type spring operation mechanism and three phase mechanical linkage operation.
LW 39-126/T 3150-31.5, 40 Outdoor HV AC SF6 Circuit Breaker Breaker is filled with SF6 gas with well arc-extinguishing and electric insulation performance. Double-circle O type seal ring is used for preventing leakage effectively.
2. Parameter (Specification) of LW 39-126/T 3150-31.5, 40 Outdoor HV AC SF6 Circuit Breaker
Mechanical parameters of circuit breaker
Table 1
No. |
Items |
Unit |
Parameters |
|
1 |
System nominal voltage |
kV |
110 |
|
2 |
Rated voltage |
kV |
126 |
|
3 |
Rated frequency |
Hz |
50 |
|
4 |
Rated current |
A |
3150 |
|
5 |
Rated short-circuit breaking current |
kA |
31.5 |
40 |
6 |
Rated short-circuit making current |
kA |
80 |
100 |
7 |
Rated short time withstand current/time |
kA/s |
31.5/4 |
40/3 |
8 |
Rated peak withstand current |
kA |
80 |
100 |
9 |
First-pole-to-clear factor |
|
1.5 |
|
10 |
Lightning impulse withstand voltage |
kV |
650 |
|
11 |
1min power frequency withstand voltage |
kV |
275 |
|
12 |
Creepage distance fracture/to earth |
cm/kV |
250/250 |
|
13 |
Rated operation order |
|
O-0.3s-CO -180s-CO |
|
14 |
Making time |
ms |
≤110 |
|
15 |
Breaking time |
ms |
≤65 |
|
16 |
Closing-opening time |
ms |
≤100 |
|
17 |
Closing non-simultaneity |
ms |
≤5 |
|
18 |
Opening non-simultaneity |
ms |
≤3 |
|
19 |
Fracture no of per pole |
piece |
1 |
|
20 |
Mechanical endurance |
time |
10000 |
|
21 |
SF6 gas pressure Rated value (20℃) Alarm value The lowest function pressure |
MPa MPa MPa |
0.55 0.50 0.45 |
0.60 0.55 0.50 |
23 |
SF6 moisture content |
ppm(V/V) |
≤150 |
|
24 |
SF6 yearly air leakage percentage |
|
≤1% |
|
25 |
Per set circuit-breaker SF6 gas charging weight |
kg |
9 |
11 |
26 |
Gross weight of per set circuit-breaker |
kg |
2200 |
|
27 |
Sub-static pull on wiring longitudinal terminal of circuit-breaker horizontal vertical |
N N N |
1250 750 1000 |
|
28 |
Voltage of auxiliary circuit |
V |
AC220 |
|
29 |
Opening-closing coil rated voltage rated current |
V A |
DC220 or DC110 1.29 |
|
30 |
Energy Storage motor rated voltage rated power |
V W |
AC220 or DC 220 700 |
|
31 |
Energy storage time |
s |
≤15 |
|
32 |
Heater voltage power |
V W |
AC220 100 |
|
33 |
Standards |
|
GB1984 |
Mechanical parameters of circuit breaker
Table 2
No. |
Name |
Unit |
Parameters |
1 |
Contact travel of moving-contact |
mm |
38~42 |
2 |
Main drive lever travel of mechanism |
mm |
113~118 |
3 |
Distance between opening movable and static contact |
mm |
75~80 |
3. Service condition of LW 39-126/T 3150-31.5, 40 Outdoor HV AC SF6 Circuit Breaker
Altitude ≤ 3000m
Ambient temperature -35℃~+40℃
Wind speed ≤35m/s
Daily temperature difference ≤25℃
Sunlight temperature 0.1w/cm²
Relative humidity Average (monthly): ≤ 90%
Average (daily): ≤ 95%
Ice thickness ≤ 10mm
Earthquake ≤ 9 °
Pollution grade III
4. Transport:
LW 39-126/T 3150-31.5, 40 Outdoor HV AC SF6 Circuit Breaker is separated into two packages for convenience of transport, one is three-pole arc-extinguishing chamber and another is base frame. (Cabinet frame and mechanism box is included).
To ensure product quality, each pole of the circuit breaker is filled with SF6 gas of 0.02 ± 0.01MPa in transport and storage, so valve of each pole can not be opened.
As porcelain piece is brittle materials, so in assembly & disassembly and transport, please be careful specially to prevent collisions