FN16A-12 Series indoor AC high voltage vacuum load switch has innovative design, small size, flexible installation, simple operation, with manual, electric two-function operation. With its operating mechanism CS6-1 type of CS or dedicated type, can also be directly manipulated in the back of the switch, you do not need to reprovision operating mechanism.
FN16A-12 Series indoor AC high voltage vacuum load switch
1. Product Introduction
FN16A-12 Series indoor AC high voltage vacuum load switch for AC 50Hz, rated voltage of 10kV network, can be breaking the load current, overload current and closing short-circuit current. Combination of electrical short-circuit breaking current, especially for oil-free, no maintenance required and frequent operation places.
2. Type Meaning of FN16A-12 Series indoor AC high voltage vacuum load switch
FN 16A - 12 R D / 200 - 31.5 – JS
FN: Indoor Switches
16A: Design Number
12: Rated voltage
R: fuse with load switch linkage
D: with ground
200: The maximum current rating of the fuse with (A)
31.5: rated short-circuit breaking current (kA)
J: electric (including manual)
S: manual operation (generally not noted)
3. Technical parameters of FN16A-12 Series indoor AC high voltage vacuum load switch
No. |
Item |
Unit |
Parameters |
1 |
Rated voltage |
kV |
12 |
2 |
Rated frequency |
Hz |
50 |
3 |
Rated current |
A |
630 |
4 |
Rated active load breaking current |
A |
630 |
5 |
Rated breaking current loop |
A |
630 |
6 |
5% rated active load breaking current |
A |
31.5 |
7 |
Rated cable charging breaking current |
A |
10 |
8 |
Rated capacitor breaking current |
A |
400 |
9 |
Rated no-load transformer breaking current |
|
1600kVA |
10 |
1 min Frequency withstand voltage (rms) to |
kV |
42/48 |
11 |
Full prey electrical impulse withstand voltage (peak) |
kV |
75/85 |
12 |
Rated short time withstand current (thermal stability) |
kA/s |
20/3 |
13 |
Rated peak withstand current (dynamic stability) |
kA |
50 |
14 |
Rated short-circuit current |
kA |
50 |
15 |
Rated current breaking times |
time |
10000 |
16 |
Mechanical life |
time |
10000 |
17 |
Contact permission attrition accumulation thickness |
mm |
3 |
18 |
Open and close operating torque (force) |
Nm |
120(240) |
19 |
Secondary control power voltage |
V |
AC / DC 240 |
20 |
Net weight |
kg |
61 |
21 |
Dimensions |
mm |
720 x 490 x 885 |
22 |
Package dimension |
mm |
830 x 900 x 520 |
4. Structure Introduction
FN16A-12 Series indoor AC high voltage vacuum load switch consists of a chassis vacuum interrupter, isolating switch, grounding
switch and actuator components. Through the upper and lower insulators
isolating switch fixed to the bottom frame. Vacuum interrupter chamber through
the insulator is fastened to the upper and lower frame, the upper and lower
brackets to support the installation of the insulators, increasing the product
overall structural stability. Grounding switch removable, mounted on the lower
end of the vacuum interrupter, operating mechanism mounted on the inside of the
base chassis, mechanical locking device left and right sides of the chassis.
FN16A-12RD/200-31.5 Type combination units within FN16A-12 in combination with
a high-voltage load switch current limiting fuse together the indoor high
voltage switchgear, the upper end of the fuse is fixed to the lower bracket of
the vacuum interrupter, the lower end is fixed to the seat by contacting the
insulator, lower bracket grounding switch and fuse together. Grounding switch
and disconnecting switch with mechanical interlock.
5. Technical Parameters: FN16A-12 Series indoor AC high voltage vacuum load switch - fuse combinations
No. |
Item |
Unit |
Parameters |
1 |
Rated voltage |
kV |
12 |
2 |
Rated frequency |
Hz |
50 |
3 |
Maximum rated current fuse |
A |
200 |
4 |
Rated transfer current |
A |
3150 |
5 |
Melting tube trigger opening time of the switch |
ms |
31 (0 + 5) |
6 |
Rated short circuit breaking current (expected value) |
kA |
31.5 |
7 |
Rated short-circuit current (prospective peak) |
kA |
80 |
8 |
1 min power frequency withstand voltage (rms) |
kV |
42/48 |
9 |
Lightning impulse withstand voltage (peak) to |
kV |
75/85 |
10 |
Fuse link striking output energy |
J |
2 ~ 5 |
11 |
Net weight |
kg |
75 |
12 |
Dimensions |
mm |
720 x 490 x 4065 |
13 |
Package dimension |
mm |
1115 x 900 x 520 |