KYT1 (KYN61)-40.5 kV Movable-type AC Metal-clad Switchgear is a three-phase AC 50Hz, indoor whole set distribution unit with rated voltage 40.5kV, which is used to accept and distribute electric energy in power plant ,substation and industrial and mining enterprises. It can control, protect and supervise circuits, and be used in the place need to operate frequently.
1.Introduction of KYT1 (KYN61)-40.5 kV Movable-type AC Metal-clad Switchgear
KYT1 (KYN61)-40.5 kV Movable-type AC Metal-clad Switchgear (hereinafter as “KYN61”) is 40.5kV three phase AC 50Hz distribution device and fitted with single busbar and double system. It is mainly applicable for power transmission and distribution in electric substation and mine enterprise to control, protect and monitor the circuit.
The main breaker is fitted with ZN85-40.5 or VD4-40.5 vacuum circuit breaker, Schneider SF serial, Alston FP serial SF6 circuit breaker with compact structure, superior performance and high reliability.
2. Parameter (Specification) of KYT1 (KYN61)-40.5 kV Movable-type AC Metal-clad Switchgear
Items |
Unit |
Parameters |
|
Rated Voltage |
kV |
40.5 |
|
Rated Frequency |
Hz |
50 |
|
Rated Current |
A |
1250,1600,2000 |
|
Rated Short-circuit Breaking Current |
kA |
25,31.5 |
|
Rated Making Current (Peak) |
kA |
63,80 |
|
4s Thermal Stability Current |
kA |
25,31.5 |
|
Rated Dynamic Current (Peak) |
kA |
63,80 |
|
Rated Insulation Level |
1min Power Frequency Withstand Voltage (r.m.s)(Between Phases, Phase to Earth) |
kV |
95 |
Lightning Impulse Withstand Voltage (Peak) |
kV |
185 |
|
1min Power Frequency Voltage Across the open gap (r.m.s) |
kV |
118 |
|
Lightning Impulse Withstand Voltage Across the open gap (Peak) |
kV |
215 |
|
Enclosure Protection Class |
|
Enclosure IP4X, Between Compartments IP2X |
|
Enclosure Dimension (Width*Depth*Height) |
mm |
1400*2800*2600 |
|
Type of Circuit Breaker |
|
Vacuum Circuit Breaker:ZN85-40.5 |
3. Service condition of KYT1 (KYN61)-40.5 kV Movable-type AC Metal-clad Switchgear
A. Ambient temperature: -15℃ ~40 ℃
B. Ambient humidity:
●Daily average RH less than 95%;
●Monthly average RH less than 90%
C. Altitude no higher than 1000m;
D. Seismic vibration shall not exceed 8 degree
The air around without any pollution of duty, smoke, erode or flammable air, steam or salty fog;
If the product is used at the condition not specified above, the consolations shall be done by both customer and manufacturer.
4. Features of KYT1 (KYN61)-40.5 kV Movable-type AC Metal-clad Switchgear
a. Cubicle structure is an assembly type, circuit breaker adopts handcart floor type structure.
b. KYT1 (KYN61)-40.5 kV Movable-type AC Metal-clad Switchgear matches with new type compound insulating vacuum circuit breaker, and has the advantages of good interchangeability and easy change.
c. Handcart is equipped with feed screw nut feed mechanism which makes movement of the handcart easy and prevent maloperation from damaging feed mechanism.
d. All operations will be done under the closed doors.
e. Interlockings of main switch, handcart, and between cubicles adopt coerciveness mechanical interlock, which meets the requirements of “five-prevention” function.
f. There is abundant space in cable room to connect many cables.
g. The enclosure is IP4X which will be changed to IP2X when doors of handcart are opened.
5. Transportation and storage
The following must be noted during the transportation and storage for KYT1 (KYN61)-40.5 kV Movable-type AC Metal-clad Switchgear
a)Seriously forbid turnover, upset, intense shake, and avoid accessing water resource;
b)Keep from rain to avoid moist;
c)Forbid disassembly the parts and components willingly.